Earth Loop Calculator 1.0.8

Calculate Ze, R1 + R2 and Zs, or estimate Ze from a measured supply-voltage drop under load.

1. Earthing arrangement and supply

2. Estimate Ze from voltage drop under load

Measure the supply voltage with the load disconnected, then measure it again with a known load operating. Use the actual load current where practical.

Ze ≈ (Uopen − Uload) ÷ Iload
This gives an approximate source impedance from the observed voltage change. It is most meaningful with a suitable predominantly resistive load, stable supply conditions and measurements made at the relevant supply point. It is not a substitute for the prescribed verification/testing method.

3. Circuit resistance and protection

Calculation aid only. Confirm the applicable BS 7671 requirements, protective-device characteristics, installation conditions, DNO data and measured/test values for the actual installation.